Raised Floor for Telecommunications data center applications

Date:2015-09-29 16:24:37  Visit:

Raised floors available for general purpose use typically do not address the special requirements needed for telecommunications applications. 

 

The general types of raised floors in telecommunications data centers include: stringerless, stringered, and structural platforms; and, truss assemblies.

 

Stringerless raised floors — an array of pedestals that provide the necessary height for routing cables and also serve to support each corner of the floor panels.

Stringered raised floors — a vertical array of steel pedestal assemblies (steel base plate, tubular upright, and a head) uniformly spaced on 2-foot centers and mechanically fastened to the concrete floor.

Structural platforms — members constructed of steel angles or channels that are welded or bolted together to form an integrated platform for supporting equipment.

Truss assemblies — utilizing attachment points to the subfloor to support a truss network on which the floor panels rest. The truss has high lateral strength and transfers lateral loads to the subfloor with less strain than possible with a vertical pedestal assembly.

A telecommunications facility may contain continuous lineups of equipment cabinets. The most densely populated installation configuration would consist of rows of continuous 2-foot-wide equipment cabinets with aisles that separate 2-foot-wide adjacent rows. This lineup configuration is considered to be the most densely populated in terms of square foot area and, therefore, the largest floor load anticipated for a raised floor system. Considering prorated aisle space, a single equipment cabinet will then occupy an 8-square foot (0.74-m2) floor area (4 square feet for the cabinet and 4 square feet of aisle).

 

The data center can be located in remote locations, and is subject to physical and electrical stresses from sources such as fires and from electrical faults.